Model PDP Series 200 maxDPU4E Hardware Guide
• Database save and recovery
• During installation of new software image in flash memory
• When an error condition is detected
The following two tables list LED colors states during a DPU boot and
during normal operation, respectively.
Interpreting LED Status While DPU Is Booting Windows CE
LED Green Yellow Red Off
Network A
N/A N/A Out of range CE
record is detected
during load
Current CE records
are working correctly
Network B
CE starting to load N/A N/A N/A
Network Backup N/A N/A Checksum error is
encountered in the
Code Flash
The Code Flash
Checksum is correct
Serial Port 1
Ready for Serial
Download
N/A N/A Not Ready for Serial
Download
Serial Port 2
N/A N/A N/A N/A
DI
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
All IOM LEDs Solid
Yellow – Still
Loading
Blinking –
IOM Loading
See Note
If LED never blinks,
IOM not functioning
AO/DO
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
If LED never blinks,
IOM not functioning
AI
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
If LED never blinks,
IOM not functioning
(not labeled)
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
Blinking –
IOM Loading
See Note
If LED never blinks,
IOM not functioning
Battery
CE Image Being
Launched
N/A N/A N/A
CP
N/A Ready to accept
Serial Download
Problem Reading
CE Flash
N/A
IOM
Ready to
communicate with
CP
N/A Initializing IOM
Not Currently
Operational
N/A
State
N/A N/A N/A N/A
NOTE: DI, DO, AI/Per IO and Prog IO all blink the same colors at the same time upon startup. If they display different
colors, they are flashing an IOM Error Code.