Metso Automation MAX Controls Inc. • 278590 •
A-4
Figure 2
Make sure the ByteBlaster cable is connected to the PC and DPU
or else the setup will be different.
Click on the “JTAG” pull down menu heading (top line of the
MAX+plus II window) if this is the first time that a DPU4E is
being programmed from this PC.
Select “Multi-Device JTAG Chain Setup” (See Figure 3).
Set the Device Name to “EPM7192S”.
Select “ADD”.
Select “Device 1” to highlight it.
Click the button labeled “Select Programming File…”.
Choose the filename for the CPLD file and then press OK
Click the “Change” button to make sure filename gets updated
properly and then OK
On the Main Programmer window, press the “Program” button
(See Figure 2)